Product Introduction
1.Product Introduction
HXGN15 - 12 AC metal-enclosed ring network switchgear is a switchgear with sulfur hexafluoride switch as the main switch, and the whole cabinet is insulated by air. It is suitable for power distribution automation, compact and expandable, characterized by simple structure, flexible operation, reliable interlocking and convenient installation. Satisfactory technical solutions can be provided for all kinds of different user requirements. Due to the adoption of sensing technology and protective circuit breakers, advanced technical performance and lightweight and flexible assembly solutions, the HXGN15-12 AC metal-enclosed ring switchgear can meet the changing requirements of the market.The main switches of the HXGN15-12 AC metal-enclosed ring switchgear adopt the original ABB SFG SF6 load switches, FLN series of load switches, permanent mechanical vacuum circuit breakers, GE Power/VacVB vacuum circuit breakers and so on. Vacuum Circuit Breaker, GE Power/VacVB type, and so on. HXGN15-12 AC metal-enclosed ring network switchgear is suitable for AC 50Hz, 12kv power system, widely used in industrial and civil cable switching network and power supply terminal, especially suitable for the following places: power distribution in urban residential areas, small secondary substations, open and close houses, industrial and mining enterprises, shopping malls, airports, subway, wind power, hospitals, stadiums, railways, tunnels and so on. Railroads, tunnels, etc.
HXGN15 - 12 AC metal-enclosed ring network switchgear is a switchgear with sulfur hexafluoride switch as the main switch, and the whole cabinet is insulated by air. It is suitable for power distribution automation, compact and expandable, characterized by simple structure, flexible operation, reliable interlocking and convenient installation. Satisfactory technical solutions can be provided for all kinds of different user requirements. Due to the adoption of sensing technology and protective circuit breakers, advanced technical performance and lightweight and flexible assembly solutions, the HXGN15-12 AC metal-enclosed ring switchgear can meet the changing requirements of the market.The main switches of the HXGN15-12 AC metal-enclosed ring switchgear adopt the original ABB SFG SF6 load switches, FLN series of load switches, permanent mechanical vacuum circuit breakers, GE Power/VacVB vacuum circuit breakers and so on. Vacuum Circuit Breaker, GE Power/VacVB type, and so on. HXGN15-12 AC metal-enclosed ring network switchgear is suitable for AC 50Hz, 12kv power system, widely used in industrial and civil cable switching network and power supply terminal, especially suitable for the following places: power distribution in urban residential areas, small secondary substations, open and close houses, industrial and mining enterprises, shopping malls, airports, subway, wind power, hospitals, stadiums, railways, tunnels and so on. Railroads, tunnels, etc.
2. Model and Meaning

3. Use conditions
Ambient temperature: upper limit + 40℃, lower limit - 15℃.
Maximum altitude of the equipment installation place: 1000m;
Ambient humidity: daily average relative humidity ≤ 95%, monthly average relative humidity ≤ 90%;
Seismic heat does not exceed 8 degrees;
The surrounding air should be free from corrosive or combustible gases, water vapor and other obvious pollution.
No serious filth and frequent severe vibration.
Ambient temperature: upper limit + 40℃, lower limit - 15℃.
Maximum altitude of the equipment installation place: 1000m;
Ambient humidity: daily average relative humidity ≤ 95%, monthly average relative humidity ≤ 90%;
Seismic heat does not exceed 8 degrees;
The surrounding air should be free from corrosive or combustible gases, water vapor and other obvious pollution.
No serious filth and frequent severe vibration.
4.Technical Parameters
| Name | Unit | Parameter |
|---|---|---|
| Rated Voltage | kV | 12 |
| Rated Frequency | Hz | 50 |
| Rated Current of Main Busbar | A | 630 |
| Rated Short - time Withstand Current / Duration of Main Circuit and Grounding Circuit | KA/s | 20/3, 20/20 |
| Rated Peak Withstand Current of Main Circuit and Grounding Circuit | kA | 50 |
| Rated Short - circuit Making Current of Main Circuit and Grounding Circuit | kA | 50 |
| Full - capacity Breaking Times of Load Switch | times | 100 |
| Breaking Current of Fuse | KA | 31.5, 40, 50 |
| Mechanical Life | times | 20000 |
| 1min Working Withstand Voltage (Effective Value) Time, to Ground / Isolation Break | KV | 42/48 |
| Lightning Impulse Withstand Voltage (Peak Value) Between Phases, to Ground / Isolation Break | KV | 75/85 |
| 1min Working Frequency Withstand Voltage of Secondary Circuit | KV | 2 |
5. Installation Dimension Drawing

6. Instructions for ordering
The following technical data should be provided when ordering:
main wiring scheme number, use and single line system diagram, rated voltage, rated current, rated short circuit breaking current, layout plan of the distribution room and arrangement and configuration of the switchgear, etc.;
requirements for the control, measurement and protection functions of the switchgear as well as requirements and schematic diagrams of other locking and automatic devices;
models, specifications and quantities of the main electrical components in the switchgear;
When the switchgear is used in special environmental conditions, it should be explained in detail at the time of ordering;
Other special requirements shall be explained and negotiated in detail in writing before ordering.、
main wiring scheme number, use and single line system diagram, rated voltage, rated current, rated short circuit breaking current, layout plan of the distribution room and arrangement and configuration of the switchgear, etc.;
requirements for the control, measurement and protection functions of the switchgear as well as requirements and schematic diagrams of other locking and automatic devices;
models, specifications and quantities of the main electrical components in the switchgear;
When the switchgear is used in special environmental conditions, it should be explained in detail at the time of ordering;
Other special requirements shall be explained and negotiated in detail in writing before ordering.、
7. Installation Dimensions
| Dimension | Applicable Scope |
|---|---|
| Height H (mm) | 1400 - Suitable for single - core cables |
| 1600 - Suitable for single - core cables | |
| 1800 - Suitable for three - core cables | |
| Width W (mm) | 375 - Incoming line, outgoing line |
| 500 - | |
| 750 - | |
| Depth D (mm) | 910 - |