GCS low voltage withdrawable switchgear
GCS low voltage withdrawable switchgear
GCS low voltage withdrawable switchgear
Product details
Product Introduction
1.Product Introduction 
GCS device is suitable for power distribution system in power plant, petroleum, chemical, metallurgy, textile, high-rise building and other industries. In large-scale power plants, petrochemical systems and other places with a high degree of automation, requiring interface with computers, as a three-phase AC frequency of 50 (60) Hz, rated operating voltage of 380V (400V, 660V), rated current of 4000A and below, power generation and power supply system in the distribution, centralized control of electric motors, reactive power compensation of the use of low-voltage power distribution equipment.

2. Model and meaning


3.Conditions of Use
>The ambient air temperature should not be higher than +40°C and lower than -5°C. The average temperature over a 24-hour period should not be +35°C. If it is higher than this, it should be operated at a reduced capacity according to the actual conditions. If it exceeds the average temperature of 24 hours, it should be operated with reduced capacity according to the actual situation.
>For indoor use, the altitude of the place of use shall not exceed 2000m. 
>Relative humidity of the surrounding air shall not exceed 50% when the maximum temperature is +40℃, and it is allowed to have a larger relative humidity when the temperature is lower, such as 90% when it is +20℃, and it shall be taken into account that condensation may occur due to the change of temperature. 
>The inclination of the device to the vertical plane when it is installed shall not exceed 50℃ and the whole group of cabinets is relatively level. (in accordance with GBJ232-82 standard).
>The device should be installed in a place where there is no violent vibration and shock and where the electrical components are not subject to due corrosion.

4.Technical Parameters
NameParameter
Rated voltage of main circuit (V)AC 380 (400), (660)
Rated voltage of auxiliary circuit (V)AC 220, 380 (400), DC 110, 220
Rated frequency (Hz)50(60)
Rated insulation voltage (V)660(1000)
Rated current (A) - Horizontal busbar≤4000
Rated current (A) - Vertical busbar (MCC)1000
Rated short - time withstand current of busbar (kA, 1 s)50, 80
Rated peak withstand current of busbar (kA/0.1s)105, 176
Power frequency test voltage (V/1min) - Main circuit2500
Power frequency test voltage (V/1min) - Auxiliary circuit1760
Busbar - Three - phase five - wire systemA, B, C, PE, N
































5.Mounting Dimension Drawing

6. Ordering Instructions 
The following technical information should be provided when ordering: 
the full model number of the product including the main circuit scheme number and auxiliary circuit scheme number; 
the main circuit system combination sequence diagram; 
the auxiliary circuit electrical schematic diagram; 
the list of components in the cabinet; 
the circuit voltage, current, time, and other parameters of the rectification; 
other special requirements that do not correspond to the normal use of the product.